| CIRCUIT-BREAKER, 3-POLE FOR PLANT PROTECTION IN=20A, ICU=18KA/415V WITH OVERCURRENT RELEASE AN N-REL.450A W/O AUXILIARY RELEASE RATED OPERATIONAL VOLTAGE 415V |
Model |
Product brand name | SENTRON |
Design of the overcurrent release | Thermomagnetic |
General technical data |
Number of poles | 3 |
Size of the circuit-breaker | 3VF22 |
Reference code / acc. to DIN 40719 extended according to IEC 204-2 / acc. to IEC 750 | Q |
Protection class |
Protection class IP | IP20 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 5.33 W |
Electricity |
Continuous current / rated value | 20 A |
Derating temperature / for the rated value of the continuous current | 40 °C |
Adjustable pick-up value current | |
of the current-dependent overload release / Full-scale value | 20 A |
of instantaneous short-circuit trip unit / initial value | 450 A |
of instantaneous short-circuit trip unit / Full-scale value | 450 A |
Main circuit |
Operating voltage | |
for main current circuit / at AC / at 50 Hz / maximum | 415 V |
for main current circuit / at AC / at 60 Hz / maximum | 415 V |
Auxiliary circuit |
Number of CO contacts / for auxiliary contacts | 0 |
Number of NC contacts / for auxiliary contacts | 0 |
Number of NO contacts / for auxiliary contacts | 0 |
Suitability |
Suitability for use | system protection |
Adjustable parameters |
Adjustable pick-up value current / of the current-dependent overload release / initial value | 20 A |
Product details |
Product component | |
Auxiliary switch | No |
Voltage trigger | No |
undervoltage release | No |
undervoltage release with leading contact | No |
Product function |
Product function | |
of thermal overload trip unit | Yes |
Ground fault protection | No |
for neutral conductors / Short-circuit and overload proof | No |
Overload protection | Yes |
Short circuit |
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value | 33 kA |
Maximum short-circuit current breaking capacity (Icu) | |
at 240 V / rated value | 65 kA |
at 400 V / rated value | 18 kA |
at 415 V / rated value | 18 kA |
Connections |
Type of electrical connection / for main current circuit | Other |
Mechanical Design |
Height | 90 mm |
Width | 105 mm |
Depth | 140 mm |
Mounting type | Built-in unit fixed-mounted version |
Environmental conditions |
Ambient temperature | |
during operation / minimum | -20 °C |
during operation / maximum | 70 °C |