4BU4701-2FA20-0F
POWER TRANSFORMER; PHASES:3;

From SIEMENS

POWER TRANSFORMER; PHASES:3; PN(KVA):31,5; UPRI(V):500; USEC(V):400; ISEC(A):46; UK(%):2,06; F(HZ):50...60; VECTOR GR./SHIELD WNG.:DYN5 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; VDE 0532
General technical data
Product designationpower transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A31 500
Efficiency0.97
Connection method for transformersDyn5
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Relative short-circuit voltage%2.06
Inputs
Phase number of the inputs3
Input voltage
_1 rated valueV500
Electrical input frequency
minimumHz50
maximumHz60
Outputs
Phase number of the outputs3
Output voltage
_1 rated valueV400
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C55
Protection class IPIP00
Mechanical data
Type of electrical connection
at output for main current circuitscrew-type terminals
at input for main current circuitscrew-type terminals
Mounting typescrews
Construction form of the iron core3UI 240/137
Certificates/ approvals

External links